◆ Automatic speed regulation after one-key start the turbine.
◆ Automatic excitation when the frequency reaches the set value.
◆ The circuit breaker automatically stores energy when the frequency reaches the set value.
◆Ensure to capture the first time of grid connection, accurate, fast and reliable shock-free grid connection .
◆One-key shutdown, the load is reduced to zero and the circuit breaker will automatically trip
◆AutomaticallyTrack the grid frequency and lock when the grid is offline50Hz. For the hydraulic speed governor and the speed governor controlled by the DC servo motor, the parameter 9,11 frequency modulation pulse width can be set smaller, and the frequency modulation pulse width can be set smaller for the speed controller controlled by the ordinary AC motor. The speed controller should set the pulse width of parameters 9 and 11 to be larger. For a system with a smaller moment of inertia, the frequency modulation interval of parameter 10 can be set smaller, and vice versa.
◆ This unit has various fault detection functions:
(A) Grid disconnection (grid voltage and frequency are displayed as < span style="font-size:18px;">0, the fault indication lasts for 76 seconds)
(B) The generator is offline (the generator voltage and frequency are displayed as 0, failure indication continues)
(C) Grid frequency deviation>3Hz (see grid frequency display, fault indication continues)
(D) Generator frequency deviation>5Hz (except when starting, see display, fault indication persists)
(E) The grid voltage is abnormal (over, under voltage, refer to the grid voltage display, the fault indication continues, the fault relay acts)
(F) generator overvoltage (see generator voltage display, fault indication continues, fault relay action)
These faults are not allowed to issue a synchronous closing command.