It is suitable for the protection of high and low voltage generators and switch cabinets. It is suitable for the integration of host control equipment manufacturers and automation enterprises to form a device for safe operation of the power system.
You only need to fill in your needs, purposes, we will provide personalized customization.
You can also contact us in the following ways
It is suitable for the protection of high and low voltage generators and switch cabinets. It is suitable for the integration of host control equipment manufacturers and automation enterprises to form a device for safe operation of the power system.
◆With high-end microcontroller as the core,High precision, stability and reliability; b>
◆Centralized control, simple wiring, easy installation;
◆Replaces the traditional multiple relay protection mode;
◆With over-voltage, low-voltage, over-current and overload protection functions;
◆It has the functions of speeding, high and low frequency, and short circuit protection;
◆Inverse time control is adopted for the protection of overcurrent, overload and short circuit;
◆The parameters can be modified in real time for special generators; all parameters are password protected;
◆Fault indicator, buzzer alarm, four-digit digital display three-dimensional fault judgment.
◆Digital displayGenerator voltage, current, frequency.
◆Applicable scope: All kinds of medium and small high-voltage and low-voltage generator sets
◆input signal
(1) PT voltage: a. Nominal 100V generator PT (voltage transformer) voltage
b. Nominal 230V generator phase voltage
c. Nominal 400V generator line voltage
(2) Three-phase current: nominal5A generator three-phase CT (current transformer) current signal
◆Output signal: Relay switch signal (normally open)
a. Fault output (for disconnecting grid-connected switch)
b. Flying protection output (used to control governor deceleration or "water bypass")
◆ Voltage measurement accuracy:±1%
◆ Current measurement accuracy:±2%
frequencymeasurement accuracy:±0.01%
◆Working power : AC 150V~360V DC 200V~250V
◆Power consumption : less than 6W
◆ Work Environment
Ambient temperature:-5℃~+45 °C
Relative Humidity: not more than 90% ( 40℃)
ElevationArea below 2500 meters
◆Dimensions: (long)< span style="font-size:18px;">120×(W) 120×(D) 120mm
◆. Hole size: 114×114 (113×113)