Microcomputer integrated protector
產(chǎn)品型號: GDB-2

It is suitable for the protection of high and low voltage generators and switch cabinets. It is suitable for the integration of host control equipment manufacturers and automation enterprises to form a device for safe operation of the power system.

sales network
Please select the address closest to you, and we will find the nearest dealer for you to serve you!
Province
Features

◆With high-end microcontroller as the core,High precision, stability and reliability;                                 b>

◆Centralized control, simple wiring, easy installation;

◆Replaces the traditional multiple relay protection mode;

◆With over-voltage, low-voltage, over-current and overload protection functions;

◆It has the functions of speeding, high and low frequency, and short circuit protection;

◆Inverse time control is adopted for the protection of overcurrent, overload and short circuit;

◆The parameters can be modified in real time for special generators; all parameters are password protected;

Fault indicator, buzzer alarm, four-digit digital display three-dimensional fault judgment.

Digital displayGenerator voltage, current, frequency.

technical parameter

Applicable scope: All kinds of medium and small high-voltage and low-voltage generator sets

input signal

(1) PT voltage: a. Nominal 100V generator PT (voltage transformer) voltage

b. Nominal 230V generator phase voltage

c. Nominal 400V generator line voltage

(2) Three-phase current: nominal5A generator three-phase CT (current transformer) current signal

Output signal: Relay switch signal (normally open)

      Contact Capacity:AC380V /3A  AC220V/5A  DC110V/0.8A  DC220V/0.2A 


a. Fault output (for disconnecting grid-connected switch)

b. Flying protection output (used to control governor deceleration or "water bypass")

◆ Voltage measurement accuracy:±1%

◆ Current measurement accuracy:±2%

frequencymeasurement accuracy:±0.01%

Working power : AC 150V~360V   DC 200V~250V

Power consumption : less than 6W

◆ Work Environment
       
Ambient temperature:-5℃~+45 °C
       
Relative Humidity: not more than 90% ( 40℃)
       
ElevationArea below 2500 meters
    ◆
Dimensions: (long)< span style="font-size:18px;">120×(W) 120×(D) 120mm

    ◆. Hole size: 114×114 (113×113)

Case show
  • Automatic power generation control system for hydropower station
    enlarge

    Automatic power generation control system for hydropower station

  • Automatic power generation control system for hydropower station
    enlarge

    Automatic power generation control system for hydropower station

  • Automatic power generation control system for hydropower station
    enlarge

    Automatic power generation control system for hydropower station