国产成人综合视频一区_日韩人妻AV无码区_黄页网站在线观看_拍拍拍无遮无挡视频1000_日本真人添下面视频免费_亚洲中文字幕永久无线码_成a人片在线观看www流畅_特别污特别黄网站_亚洲欧美日韩图片_日韩乱码一区中文字幕

Shenzhen Guodian Xuzhen Electric Technology Co., Ltd.

Product

product demand

We can customize according to your needs, please fill in the form below.

Why Customize?

You only need to fill in your needs, purposes, we will provide personalized customization.

contact us

You can also contact us in the following ways

support hotline:
TEL:400-698-3738
Shenzhen Guodian Xuzhen Electric Technology Co., Ltd. Address:
龍崗區(qū)龍城街道五聯瓦窯東路26號安能泰工業(yè)園
Microcomputer intelligent quasi-synchronized controller
產品型號: PTQ2000A1

In the power system, the parallel operation of synchronous generator and line transformer is often carried out. In order to ensure the safe and rapid integration of the synchronous generator into the grid, a quasi-synchronous controller must be used.
The PTQ2000A1 microcomputer intelligent quas...

sales network
Please select the address closest to you, and we will find the nearest dealer for you to serve you!
Province
Features

◆Ensure to capture the first time of grid connection, accurate, fast, reliable and shock-free grid connection;

◆Automatic variable parameter frequency modulation, voltage regulation, accurate prediction of closing phase angle;

◆It can be used for low voltage 400V, high voltage 100V, single generator, single line closing and grid connection;

◆The synchronization parameters that can be set according to the requirements are: allowable pressure difference, allowable frequency difference, the actual rated voltage of the TV on the side to be paralleled, the actual rated voltage of the TV on the system side, Overvoltage protection value, TV secondary voltage angle of system side, allowable power angle;

◆This device has power grid disconnection, generator disconnection, grid frequency deviation > 3Hz, generator frequency deviation > 5Hz, abnormal grid voltage, and excessive generator overvoltage. Various fault detection functions: these faults are not allowed to issue a synchronous closing command.

◆With generator voltage, generator frequency, grid voltage, grid frequency, generator and grid voltage difference, generator and grid frequency difference, generator and grid phase difference number display function.

◆The parameters can be modified in real time for special generators; all parameters are password protected;


This unit has various fault detection functions:

1) The power grid is offline (the grid voltage and frequency are displayed as 0, and the fault indication is maintained for 76 seconds )
(2) Generator offline (generator voltage and frequency are displayed as 0, and the fault indication continues )
(3) grid frequency deviation>3Hz (refer to grid frequency display, fault indication continues)< /span>
4) generator frequency deviation>5Hz (except when starting, see display, fault Instructions continue)
5) The grid voltage is abnormal (over, under voltage, see the grid voltage display, the fault indication continues , fault relay action)
Generator overvoltage (see generator voltage display, fault indication continues, fault relay action)
These faults are not allowed to issue a synchronous closing command.


technical parameter
◆Power supply voltage: AC110V~280V/50HZ DC:110V~280V
◆Input Signal:
Generator (to be paralleled) standard voltage:0V~100V+30V 0V~400V+120V  ;
Grid (system side) standard voltage:0V~100V+30V 0V~400V+120V < /span>
◆Voltage measurement accuracy: no less than ±0.2%
◆Frequency measurement accuracy: no less than ±0.2%
◆Power consumption: less than 6W
◆Working Environment
Ambient temperature:-20℃~﹢50℃
Relative humidity: no more than90% (40℃)
ElevationArea below 4000 meters
Case show
  • Automatic power generation control system for hydropower station
    enlarge

    Automatic power generation control system for hydropower station

  • Automatic power generation control system for hydropower station
    enlarge

    Automatic power generation control system for hydropower station

  • Automatic power generation control system for hydropower station
    enlarge

    Automatic power generation control system for hydropower station