parameter 0, debugging parameter, generator (to be paralleled) voltage measurement correction, it is used to correct the manufacturing error of the generator voltage measurement circuit, users generally cannot enter this parameter. When debugging, first enter this parameter, the setting range of this parameter is ±12.5%, and the setting accuracy is 0.1%, but this parameter itself is not displayed, but the measured value of generator voltage is displayed, so as long as this parameter is adjusted so that the displayed value is the same as the actual value That's it, very convenient. Note that if the difference between the displayed value and the actual value exceeds ±8%, it is better to modify the measured voltage divider resistance first, and then adjust this parameter.
◆Parameter 1, debugging parameters, grid (system side) voltage measurement correction, which is used to correct the manufacturing error of the grid voltage measurement circuit. Similarly, the user cannot enter, and the others are similar to parameter 0.
◆ Parameter 2, multi-channel/single-channel selection (display 8888/1111), the factory setting is set to multi-channel/single-channel according to user requirements.
◆Parameter 3, closing manual/automatic selection (display HE--/HEAU), the factory setting is automatic.
◆Parameter 4, manual approval for closing (display HE11/HE00, HE11 requires approval), the factory setting is no approval.
◆Parameter 5, allow/disallow closing without pressure (display HU11/HU00, HU11 is allowed), the factory setting is not allowed.
◆Parameter 6, the baud rate setting (displayed as 1200, 2400, 4800, 9600) is factory set to 2400.
◆Parameter 7, generator frequency modulation (speed) manual/automatic selection (display TF--/TFAU), manual is not allowed to work, the factory setting is automatic.
◆Parameter 8, generator voltage regulation manual/automatic selection (TU--/TUAU is displayed), manual is not allowed to work, the factory setting is automatic.
◆Parameter 9, generator voltage regulation mode selection: digital/analog regulation (display dddd/AAAA). The corresponding adjustment parameter of digital adjustment is parameter 23; the analog adjustment is pulse width adjustment, and the corresponding adjustment parameter is parameter 24. The factory setting is analog adjustment.
◆Parameter 10, when digital voltage regulation mode is selected, count/(special) pulse width regulation selection (display CCCC/PPPP). Count adjustment uses parameter 23 as the basic adjustment count; pulse width adjustment uses parameter 23 as the basic adjustment strength index, and uses parameters 24 and 25 to simulate the continuous plus (continuously minus) button action pulse width in line with the adjustment strength. This parameter does not appear when analog adjustment is selected, and the factory setting count adjustment.
◆Parameter 11, 1# channel working mode selection: line/generator (display EEEE/FFFF), usually when the user enters the parameter setting state, first enter this working mode selection. The factory setting is generator mode. Although in principle, 1# channel can be set to any working mode, but in the case of multiple channels, we stipulate: if at least one of the channels is a generator, the 1# channel must be selected as the generator working mode (the rest are optional); In the case of all lines, if at least one of them is a line difference frequency grid connection, the 1# channel must be selected as the difference frequency grid connection mode.
◆Parameter 12, 1# channel grid (system side) voltage sampling corner/no corner selection (display PH11/PH00), the factory setting is no corner.
◆ Parameter 13, 1# channel grid (system side) voltage sampling when selecting the corner, the corner +30°/-30° (display 30°/-30°), The factory setting is -30°.
◆Parameter 14, when channel 1 selects the line working mode, the difference frequency/same frequency grid connection is selected, dF11/dF00 is displayed, and the factory setting is the same frequency. This parameter does not appear when the 1# channel is selected as the generator working mode.
◆ Parameter 15, 1# channel lead time setting, the setting range is 0.05S~0.8S, and the setting precision is 0.01S. The lead time is used to compensate a series of time delays from the closing command of the quasi-synchronized device to the actual closing, and the factory setting is 0.3S. If the "Synchronous feedback" signal is connected, the device will automatically modify this parameter after the synchronous closing is successful.
◆Parameter 16, the rated voltage setting of the 1# channel generator (to be paralleled), the setting range is 50V~125V, and the setting accuracy is 0.5V. The general standard PT voltage is 100V. Due to the possible manufacturing error of the sampling voltage transformer, as well as the "line voltage"/"phase voltage", △/Y connection method, etc., the sampling voltage corresponding to the rated voltage is not 100V, how much is set? . The factory setting is 100V.
◆ Parameter 17, 1# channel grid (system side) rated voltage setting, the setting range is 50V ~ 125V, the setting accuracy is 0.5V, similar to parameter 16. The factory setting is 100V.
◆ Parameter 18, generator allowable frequency difference setting, the setting range is ±0.05Hz~±0.6Hz, and the setting accuracy is 0.01Hz. The factory setting is 0.2Hz. But when the 1# channel is set to the line difference frequency grid connection work mode, this parameter should be set to "line frequency difference", the setting range is ±0.02Hz~±0.3Hz, and the setting accuracy is 0.01Hz.
◆Parameter 19, generator allowable voltage difference setting, the setting range is 1%~8% of rated voltage. Set the accuracy to 0.1%. The system will adjust the positive deviation according to this set value (the positive deviation is 1.5 times the set value, and the negative deviation is 0.5 times the set value), and the factory setting is 3%. However, when the 1# channel is set to the line working mode, this parameter should be set as "line pressure difference", the setting range is ±1%~±18%, and the setting accuracy is 0.1%.
parameter 20, generator (line difference frequency grid-connected) allowable closing phase difference setting, the setting range is ±1.0°~±6.0°, and the setting accuracy is 0.1 °. The factory setting is 3.0°. However, when the 1# channel is set to the working mode of line co-frequency and grid connection, this parameter should be set to "power angle", the setting range is 10°~60°, and the setting accuracy is 1°. Parameters 18, 19, and 20 are generally used for generator parameter settings, and parameters 42, 43, and 44 are generally used for similar circuit parameter settings. However, the settings of parameters 18, 19 and 20 are always consistent with the working mode selection of 1# channel, when all 8 channels are connected to the grid at the same frequency When 1# channel takes parameters18, 19, 20, other channels take parameters 42, 43, 44. Therefore, this arrangement is made to only take the first 27 parameters when working with a single channel.
Parameter 21, generator frequency modulation pulse width setting, the setting range is 0.1S~0.8S, the basic adjustment interval is 1S, the setting accuracy is 0.01S, variable coefficient adjustment . The factory setting is 0.3S.
◆Parameter 22, closing width setting, the setting range is 0.2S~1S, the setting precision is 0.01S, and the factory setting is 0.5S.
parameter 23, the generator digital voltage regulation coefficient setting, the setting range is 2~10, the setting precision is 1, it is valid when the parameter 9 is set to digital voltage regulation, it leaves the factory Set to 6.
◆ Parameter 24, generator analog voltage regulation pulse width (digital single-shot voltage regulation pulse width) setting, the setting range is 0.1S~0.8S, and the setting accuracy is 0.01 S, when parameter 9 is set to analog voltage regulation, its meaning is the analog voltage regulation pulse width, and the factory setting is 0.3S. When parameter 9 is set to digital voltage regulation and parameter 10 is set to pulse width voltage regulation, its meaning is digital single-shot voltage regulation pulse width. Equivalent to the digital potentiometer ±1 digit when the button is pressed the maximum time our company's digital potentiometer is designed to be 0.3S
Number 25, the incremental pulse width setting of the generator digital voltage regulation, the setting range is 0.02S~0.2S, the setting accuracy is 0.01S, and the factory setting is 0.06 S, the value of our company's digital potentiometer is designed to be 0.06S. It is valid when parameter 9 is set to digital voltage regulation and parameter 10 is set to pulse width voltage regulation, and this parameter does not appear in other settings. It cooperates with parameter 24 "digital single-shot voltage regulation pulse width" to complete the preparation of "digital special pulse width". Assuming that "digital single-shot voltage regulation pulse width" is set to TA, this parameter is set to TB, if parameter 23 Digital voltage regulation coefficient K=1, then "digital special pulse width" T=TA-0.01; K=2, T= TA-0.01+TB; K=3, T=TA-0.01+2TB …
Parameter 26, generator (to be paralleled) overvoltage value setting, it means the ratio of overvoltage value to rated voltage, the setting range is 110%~130 %. The factory setting is 120%.
◆Parameter 27, equipment number setting, the setting range is 0~99, the factory setting is 10.
◆Parameter 28, 2# channel working mode selection: line/generator (display EEEE/FFFF), the factory setting is generator mode.
◆Parameter 29, 2# channel grid (system side) voltage sampling corner/no corner selection (display PH11/PH00), the factory setting is no corner.
◆ Parameter 30, when the voltage sampling of the 2# channel grid (system side) selects the corner, the corner is +30°/-30° (display 30°/-30°), The factory setting is -30°.
◆When parameter 31, 2# channel selects the line working mode, the difference frequency/same frequency grid connection selection, displays dF11/dF00, the factory setting 8 is the same frequency. This parameter does not appear when the 2# channel is selected as the generator working mode.
◆Parameter 32, 2# channel lead time setting, the setting range is 0.05S~0.8S, and the setting precision is 0.01S. The factory setting is 0.3S. If the "Synchronous feedback" signal is connected, the device will automaticallyModify this parameter manually.
◆ Parameter 33, 2# channel generator (to be paralleled) rated voltage setting, the setting range is 50V~125V, and the setting accuracy is 0.5V. The factory setting is 100V.
◆Parameter 34, 2# channel grid (system side) rated voltage setting, the setting range is 50V~125V, and the setting accuracy is 0.5V. The factory setting is 100V.
◆ Parameter 35, 3# channel working mode selection: line/generator (display EEEE/FFFF), the factory setting is line mode.
◆ Parameter 36, 3# channel grid (system side) voltage sampling corner/no corner selection (display PH11/PH00), the factory setting is no corner.
◆ parameter 37, when the voltage sampling of the 3# channel grid (system side) selects the corner, the corner is +30°/-30° (display 30°/-30°), The factory setting is -30°.
◆ When parameter 38, 3# channel selects the line working mode, the difference frequency/same frequency grid connection is selected, and dF11/dF00 is displayed, and the factory setting is the same frequency. This parameter does not appear when the 3# channel is selected as the generator working mode.
◆Parameter 39, 3# channel lead time setting, the setting range is 0.05S~0.8S, and the setting precision is 0.01S. The factory setting is 0.3S. If the "Synchronous feedback" signal is connected, the device will automatically modify this parameter after the synchronous closing is successful.
◆Parameter 40, 3# channel generator (to be paralleled) rated voltage setting, set The range is 50V~125V, . The setting precision is 0.5V. The factory setting is 100V.
◆Parameter 41, 3# channel grid (system side) rated voltage setting, the setting range is 50V~125V, and the setting accuracy is 0.5V. The factory setting is 100V.
◆Parameter 42, the allowable frequency difference setting of line difference frequency grid connection, the setting range is ±0.02Hz~±0.3Hz, and the setting accuracy is 0.01Hz. The factory setting is 0.1Hz.
◆ Parameter 43, the setting of the allowable voltage difference of the line grid connection, the setting range is ±1%~±18% of the rated voltage, and the setting accuracy is 0.1%. The factory setting is ±5%
parameter 44, the "power angle" setting of line co-frequency grid connection, the setting range is 10°~60°, the setting accuracy is 1°, and the factory setting is 30 °. This parameter can be temporarily modified by the host computer on site until 80°. But (after a power outage) it doesn't save.
◆Parameter 45, 4# channel working mode selection: line/generator (display EEEE/FFFF), the factory setting is line mode.
◆Parameter 46, 4# channel grid (system side) voltage sampling corner/no corner selection (display PH11/PH00), the factory setting is no corner.
◆ parameter 47, when the voltage sampling of channel 4# channel grid (system side) selects the corner, the corner is +30°/-30° (display 30°/-30°), The factory setting is -30°. 9
◆ When parameter 48, 4# channel selects the line working mode, the difference frequency/same frequency grid connection is selected, dF11/dF00 is displayed, and the factory setting is the same frequency. This parameter does not appear when the 4# channel is selected as the generator working mode.
◆Parameter 49, 4# channel lead time setting, the setting range is 0.05S~0.8S, and the setting precision is 0.01S. The factory setting is 0.3S. If the "Synchronous feedback" signal is connected, the device will automatically modify this parameter after the synchronous closing is successful.
◆Parameter 50, 4# channel generator (to be paralleled) rated voltage setting, the setting range is 50V~125V, and the setting accuracy is 0.5V. The factory setting is 100V.
◆Parameter 51, 4# channel grid (system side) rated voltage setting, the setting range is 50V~125V, and the setting accuracy is 0.5V. The factory setting is 100V.
◆Parameter 52, 5# channel working mode selection, similar to parameter 45.
◆Parameter 53, 5# channel grid (system side) voltage sampling corner/no corner selection, similar to parameter 46.
◆Parameter 54, when the voltage sampling of channel 5# channel grid (system side) selects the corner, the corner is +30°/-30°, similar to parameter 47.
◆When parameter 55, 5# channel selects the line working mode, the difference frequency/same frequency grid connection selection, the factory setting is the same frequency. Similar to parameter 48.
◆Parameter 56, 5# channel lead time setting, similar to parameter 49.
◆Parameter 57, 5# channel generator (to be paralleled) rated voltage setting, similar to parameter 50.
◆Parameter 58, 5# channel grid (system side) rated voltage setting, similar to parameter 51.
◆Parameter 59, 6# channel working mode selection, similar to parameter 45.
◆Parameter 60, 6# channel grid (system side) voltage sampling corner/no corner selection, similar to parameter 46.
◆Parameter 61, when the voltage sampling of channel 6# channel grid (system side) selects the corner, the corner is +30°/-30°, similar to parameter 47.
◆When parameter 62, 6# channel selects the line working mode, the difference frequency/same frequency grid connection selection, the factory setting is the same frequency. Similar to parameter 48.
◆Parameter 63, 6# channel lead time setting, similar to parameter 49.
◆Parameter 64, 6# channel generator (to be paralleled) rated voltage setting, similar to parameter 50.
◆Parameter 65, 6# channel grid (system side) rated voltage setting, similar to parameter 51.
◆Parameter 66, 7# channel working mode selection, similar to parameter 45.
◆Parameter 67, 7# channel grid (system side) voltage sampling corner/no corner selection, similar to parameter 46.
◆Parameter 68, 7# channel grid (system side) voltage sampling when selecting the corner, the corner is +30°/-30°, similar to parameter 47.
◆When parameter 69, 7# channel selects the line working mode, the difference frequency/same frequency grid connection selection, the factory setting is the same frequency. Similar to parameter 48.
◆Parameter 70, 7# channel lead time setting, similar to parameter 49.
◆Parameter 71, 7# channel generator (to be paralleled) rated voltage setting, similar to parameter 50.
◆Parameter 72, 7# channel grid (system side) rated voltage setting, similar to parameter 51.
◆Parameter 73, 8# channel working mode selection, similar to parameter 45.
75. Parameter 74, 8# channel grid (system side) voltage sampling corner/no corner selection, similar to parameter 46. 10
◆Parameter 75, 8# channel grid (system side) voltage sampling selects the corner when the corner is +30°/-30°, similar to parameter 47.
◆When parameter 76, 8# channel selects the line working mode, the difference frequency/same frequency grid connection selection, the factory setting is the same frequency. Similar to parameter 48.
◆Parameter 77, 8# channel lead time setting, similar to parameter 49.
◆Parameter 78, 8# channel generator (to be paralleled) rated voltage setting, similar to parameter 50.
◆Parameter 79, 8# channel grid (system side) rated voltage setting, similar to parameter 51.
Device Specifications
◆Power:
AC85V~250V DC100V~250V
◆Input PT signal:
Generator (to be paralleled) standard voltage: 0V~100V+30V
Grid (system side) standard voltage: 0V~100V+30V
◆Input synchronous feedback signal: closing auxiliary normally open contact signal
◆Output signal: speed-up, speed-down, boost, step-down synchronous closing and fault six contact signals, output in relay mode,
The contact capacity is AC resistive 220V/5A; AC resistive 380V/2A; DC 110V/0.8A, DC 220V/0.2A.
◆For other conditions, please refer to the industry standard of the former Ministry of Machinery Industry JB/T 3950-1999 "Automatic quasi-synchronization device".